Estimate voltage loss along a wire run
Use this voltage drop calculator to compare a wire size before planning a small electrical or maker project. Choose copper or aluminum, an AWG size, the one-way distance in feet and the current flowing through the load. Select 120 or 240 V single-phase AC, or 12 or 24 V DC. The loaded example shows the estimated volts lost in the wires, the percentage of supply voltage lost and the voltage remaining at the load. Answers update as you edit, without sending your inputs to a server.
This is a resistance-only estimate at 20°C (68°F). It is not a substitute for local electrical code, a cable manufacturer's data or a qualified electrician. A result below a chosen percentage does not mean a wire is safe for the current, approved for the installation or compatible with the terminals. Keep voltage drop and electrical safety checks separate throughout your planning.
Enter the distance once
Measure from the supply to the load along the actual cable route. Enter that one-way length, including bends and routing allowances. The calculation already includes an equal-length return conductor. Doubling the distance before entering it counts the return twice and overstates the result. For a DC circuit, the return is the negative wire. For a simple single-phase circuit, current also travels through two conductors; the model applies the same loop-resistance calculation.
Enter the expected operating current rather than automatically using a breaker rating. This calculator holds current constant. It does not solve how a motor, heater, LED driver or regulated power supply changes its current when its terminal voltage changes. Starting current and brief surges may need a separate calculation using equipment data. A shared-neutral circuit with unbalanced loads is outside this model.
Worked example: a copper run
The loaded example uses 12 AWG copper, a 100 ft one-way run, a 15 A load and a 120 V supply. Running the calculator library gives a loop resistance of approximately 0.317625 Ω. Multiplying by current gives 4.764 V dropped, or 3.970% of the supply. Estimated voltage at the load is 115.236 V. Displayed values are rounded; wire comparisons use the unrounded results.
For the same current and distance, the thinnest modeled wire under 3% is 10 AWG. The thinnest under 5% is 12 AWG. Change the selected size to 10 AWG and the library gives 2.996 V dropped, 2.497% drop and 117.004 V at the load. These are voltage-drop comparisons, not statements about which conductor a circuit requires. Consult installation requirements before selecting or purchasing cable.
Compare material and supply voltage
Keeping the loaded example's size, distance and current but choosing aluminum gives approximately 7.804 V dropped, 6.504% drop and 112.196 V at the load. The modeled sizes under the two targets become 8 AWG and 10 AWG respectively. Aluminum uses a different resistivity; this selector does not establish whether aluminum conductors or a particular size are allowed for your application. Connections and equipment must be suitable for the actual conductor material.
Changing only the copper example's supply to 240 V leaves the calculated wire loss at 4.764 V but reduces the percentage to 1.985%. At 12 V, that same wire loss is 39.703%, leaving only 7.236 V in the constant-current model. This illustrates why a long low-voltage cable can need substantial conductor area. Raising a system voltage requires compatible equipment and proper design, not simply changing a calculator setting.
Read the AWG comparison carefully
A lower AWG number means a thicker conductor. The calculator searches every whole gauge from 40 down to 0 and returns the thinnest wire whose unrounded percentage is strictly below each target. It includes odd gauges, which may not be readily stocked for your cable type. If no size passes, it reports no match within AWG 0–40. It does not extrapolate to larger 2/0, 3/0 or 4/0 conductors. Zero AWG is also called 1/0.
The 3% and 5% labels are comparison targets, not a universal legal rule. This calculation covers one entered run. It does not account for voltage already lost in an upstream feeder. For nominal wire dimensions and resistance, open the AWG wire gauge calculator. For a circuit board rather than a cable, use the separate PCB trace width calculator.
Understand the model's limits
Resistance is resistivity times conductor length divided by cross-sectional area. The tool reuses the tested nominal AWG geometry and copper resistance library. Aluminum uses 2.824 × 10⁻⁸ Ω·m, from the US Bureau of Mines electrical safety handbook. Both material assumptions refer to 20°C. Warm conductors, actual alloy, stranding and manufacturing tolerances can change resistance. Connector losses are excluded.
AC results assume unity power factor and omit reactance and skin effect. Three-phase systems and parallel conductors are not supported. If the calculated drop exceeds the supply, the tool flags the constant-current assumption rather than presenting a negative load voltage. Before building, check actual cable data, operating temperature, equipment voltage tolerance, ampacity, protection, grounding and local installation requirements.