Wire Voltage Drop Calculator

Electronics

Estimate copper or aluminum wire voltage drop by AWG, feet and amps for 120/240 V AC or 12/24 V DC. Compare wire sizes under 3% and 5% drop targets.

Estimated wire voltage drop

4.764 V (3.97%)

Voltage at load: 115.236 V

Copper, 12 AWG · 100 ft one way · 15 A · 120 V single-phase AC

Estimate at 20°C (68°F), with equal outgoing and return wires. Warm wires can drop more voltage. This is not a substitute for local electrical code or a qualified electrician.

Thinnest wire under each drop target

Under 3% drop
10 AWG
Under 5% drop
12 AWG

Voltage-drop comparison only, within AWG 0–40. Lower AWG numbers mean thicker wire. Odd gauges may be hard to buy. These results do not establish ampacity, availability or permission to use aluminum.

Formula and assumptions

Drop = current × loop resistance. Loop resistance = resistivity × (2 × one-way length) ÷ wire area. AC assumes a resistive load at unity power factor; reactance and skin effect are omitted. No three-phase, shared neutral, parallel wires, connector losses or temperature correction.

Copper: 1.724 × 10⁻⁸ Ω·m. Aluminum: 2.824 × 10⁻⁸ Ω·m. Both at 20°C, using nominal AWG geometry. US Bureau of Mines resistivity reference. Actual cable resistance can differ.

3% and 5% are comparison targets, not a code compliance verdict. Check the complete feeder and branch circuit, conductor ampacity, terminals, insulation, installation and local requirements separately.

On this browser only

Give feedback

Did this tool help?

Tell us what worked, what didn’t, or what you’d like next.

Opens Google Forms in a new tab with this tool’s name filled in. No sign-in or email required. Feedback is optional.

How to use Wire Voltage Drop Calculator

  1. 1Choose copper or aluminum and the wire gauge. The loaded example uses copper 12 AWG.
  2. 2Enter one-way length in feet and actual load current in amps. The return wire is included automatically.
  3. 3Choose 120/240 V single-phase AC or 12/24 V DC and read the estimate above the fields.
  4. 4Compare the thinnest sizes under each drop target, then check ampacity and local electrical code separately.

About Wire Voltage Drop Calculator

Estimate voltage loss along a wire run

Use this voltage drop calculator to compare a wire size before planning a small electrical or maker project. Choose copper or aluminum, an AWG size, the one-way distance in feet and the current flowing through the load. Select 120 or 240 V single-phase AC, or 12 or 24 V DC. The loaded example shows the estimated volts lost in the wires, the percentage of supply voltage lost and the voltage remaining at the load. Answers update as you edit, without sending your inputs to a server.

This is a resistance-only estimate at 20°C (68°F). It is not a substitute for local electrical code, a cable manufacturer's data or a qualified electrician. A result below a chosen percentage does not mean a wire is safe for the current, approved for the installation or compatible with the terminals. Keep voltage drop and electrical safety checks separate throughout your planning.

Enter the distance once

Measure from the supply to the load along the actual cable route. Enter that one-way length, including bends and routing allowances. The calculation already includes an equal-length return conductor. Doubling the distance before entering it counts the return twice and overstates the result. For a DC circuit, the return is the negative wire. For a simple single-phase circuit, current also travels through two conductors; the model applies the same loop-resistance calculation.

Enter the expected operating current rather than automatically using a breaker rating. This calculator holds current constant. It does not solve how a motor, heater, LED driver or regulated power supply changes its current when its terminal voltage changes. Starting current and brief surges may need a separate calculation using equipment data. A shared-neutral circuit with unbalanced loads is outside this model.

Worked example: a copper run

The loaded example uses 12 AWG copper, a 100 ft one-way run, a 15 A load and a 120 V supply. Running the calculator library gives a loop resistance of approximately 0.317625 Ω. Multiplying by current gives 4.764 V dropped, or 3.970% of the supply. Estimated voltage at the load is 115.236 V. Displayed values are rounded; wire comparisons use the unrounded results.

For the same current and distance, the thinnest modeled wire under 3% is 10 AWG. The thinnest under 5% is 12 AWG. Change the selected size to 10 AWG and the library gives 2.996 V dropped, 2.497% drop and 117.004 V at the load. These are voltage-drop comparisons, not statements about which conductor a circuit requires. Consult installation requirements before selecting or purchasing cable.

Compare material and supply voltage

Keeping the loaded example's size, distance and current but choosing aluminum gives approximately 7.804 V dropped, 6.504% drop and 112.196 V at the load. The modeled sizes under the two targets become 8 AWG and 10 AWG respectively. Aluminum uses a different resistivity; this selector does not establish whether aluminum conductors or a particular size are allowed for your application. Connections and equipment must be suitable for the actual conductor material.

Changing only the copper example's supply to 240 V leaves the calculated wire loss at 4.764 V but reduces the percentage to 1.985%. At 12 V, that same wire loss is 39.703%, leaving only 7.236 V in the constant-current model. This illustrates why a long low-voltage cable can need substantial conductor area. Raising a system voltage requires compatible equipment and proper design, not simply changing a calculator setting.

Read the AWG comparison carefully

A lower AWG number means a thicker conductor. The calculator searches every whole gauge from 40 down to 0 and returns the thinnest wire whose unrounded percentage is strictly below each target. It includes odd gauges, which may not be readily stocked for your cable type. If no size passes, it reports no match within AWG 0–40. It does not extrapolate to larger 2/0, 3/0 or 4/0 conductors. Zero AWG is also called 1/0.

The 3% and 5% labels are comparison targets, not a universal legal rule. This calculation covers one entered run. It does not account for voltage already lost in an upstream feeder. For nominal wire dimensions and resistance, open the AWG wire gauge calculator. For a circuit board rather than a cable, use the separate PCB trace width calculator.

Understand the model's limits

Resistance is resistivity times conductor length divided by cross-sectional area. The tool reuses the tested nominal AWG geometry and copper resistance library. Aluminum uses 2.824 × 10⁻⁸ Ω·m, from the US Bureau of Mines electrical safety handbook. Both material assumptions refer to 20°C. Warm conductors, actual alloy, stranding and manufacturing tolerances can change resistance. Connector losses are excluded.

AC results assume unity power factor and omit reactance and skin effect. Three-phase systems and parallel conductors are not supported. If the calculated drop exceeds the supply, the tool flags the constant-current assumption rather than presenting a negative load voltage. Before building, check actual cable data, operating temperature, equipment voltage tolerance, ampacity, protection, grounding and local installation requirements.

Frequently asked questions

Do I enter one-way or round-trip wire length?

Enter the one-way distance in feet. The calculator doubles it internally for equal outgoing and return conductors.

Does this work for 120 V and 240 V circuits?

Yes, for a simplified single-phase resistive load at unity power factor. It omits reactance, skin effect and starting transients; it does not support three-phase or shared-neutral circuits.

Can I estimate 12 V or 24 V DC voltage drop?

Yes. Select the DC supply voltage and enter the actual load current. The model assumes two equal wires and constant current.

Does a 3% result mean my wiring meets code?

No. The targets compare voltage loss only. Check local electrical code, ampacity, conductor type, protection, terminals and the complete installation separately with a qualified electrician.

Why does aluminum give a higher voltage drop?

Its modeled resistivity is higher than copper at the same temperature and conductor area. Actual cable resistance depends on alloy, construction and operating temperature.

What does smallest AWG mean here?

It means the thinnest conductor, which has the largest AWG number that passes the selected target. Lower AWG numbers are thicker. Results include odd gauges and are limited to AWG 0–40.

Are 3% and 5% inclusive limits?

No. This tool searches for drop strictly under each target, using unrounded calculations. A displayed rounded percentage can look equal to a target even when the underlying result differs.

Does the suggested wire size include ampacity?

No. The comparison ignores ampacity, insulation, bundling, terminals and installation conditions. A wire that meets a drop target can still be unsuitable or unsafe.

Why does the calculator flag a drop above the supply?

The constant-current model has exceeded the available voltage. Actual current and load behavior must be solved separately; a negative load voltage would not be a useful prediction.

Does this account for warm wires and connector losses?

No. It uses nominal conductor resistance at 20°C (68°F), excluding connections. Warm wires can have greater resistance. Use manufacturer cable data and an installation-specific calculation for final design.

Have a suggestion for Wire Voltage Drop Calculator?Share your feedback ↗